Fault Analysis and Improvement Measures of GIL Three-pillar Insulator in UHVDC Transmission Project
With the increasingly in-depth construction of UHVDC transmission project
Gas Insulated TransmissionLine(GIL)has been widely used in UHVDC transmission system due to its advantages such as small area
good en-vironmental compatibility
large transmission capacity
high voltage and large current
etc
and the study on its op-erational stability has been put on the schedule. In order to analyze the reasons for the fault of the three-pillar insula-tor during the operation of GIL and study the operation characteristics of the three-pillar insulator
the internal manu-facturing defect of the three-pillar insulator was identified as the cause of the fault through the analysis of partial dis-charge of GIL ultrasonic wave
disintegration inspection
force analysis of the fixed three-pillar insulator and produc-tion process analysis of the fixed three-pillar insulator. The analysis shows that through the measures of GIL fixedthree-pillar assembly optimization
insulation pillar production process optimization and fixed-three-pillar plate opti-mization
the improved three-pillar insulator applied to the production site can effectively reduce the equipment fail-ure rate of GIL
improve the operation stability of GIL
which is of great significance to the reliable operation of UH-VDC transmission project.