ZHANG Junqiang, DONG Zhuoyuan, SHENG Fei, et al. Research on Cross-connection Grounding Modes of Long-distance 330 kV Cable Sheath and Layout Optimization of Return Cable[J]. High voltageapparatus, 2020, 56(2): 189-196.
ZHANG Junqiang, DONG Zhuoyuan, SHENG Fei, et al. Research on Cross-connection Grounding Modes of Long-distance 330 kV Cable Sheath and Layout Optimization of Return Cable[J]. High voltageapparatus, 2020, 56(2): 189-196. DOI: 10.13296/j.1001-1609.hva.2020.02.028.
Research on Cross-connection Grounding Modes of Long-distance 330 kV Cable Sheath and Layout Optimization of Return Cable
To design long-distance 330 kV cable line rationally and standardly and provide selection basis of the devices such as cable sheath protector
two cross-connection modes of the 330 kV cable sheath are studied.Firstly
according to the existing 330 kV cable parameters and laying method of cable in tunnel
the electromagnetic transient analysis software EMTP-ATP is used for simulation modeling
and the sheath ’ s induced voltage of each point of the line in normal operation is analyzed to obtain the voltage ’ s distribution laws and characteristics for two sheath grounding modes.Secondly
in the case that a single-phase short-circuit grounding fault occurs in the system
the features and distribution laws of the sheath’s induced voltage waveforms of the faulty line and normal line are discussed.The induced voltage data under the two grounding modes are compared
and the effects of the line length on the distribution law and the value of the induced voltage are analyzed.Thirdly
a return cable layout method is proposed for the single-end protected grounding mode
and the influences of the additional return cable and the return cable relocation on the system are investigate.It is concluded that the direct grounding mode at both ends of the sheath has relatively low induced voltage in steady state and transient fault state
and has high economical efficiency
so it can be taken as the preferred grounding mode for the 330 kV cable sheath.For the single-end grounding mode
the addition of return cable can reduce the induced voltage of the cable sheath when fault occurs
and return cable relocation can reduce the circulating current during steady-state operation.
Analysis of Three-phase Unbalance Issue of Grounding Current of Submarine and Land Cable Transition Joint
Calculation and Measurement Analysis for Induced Voltage and Current of 500 kV/220 kV Mixed-voltage and Four-circuit Transmission Lines on the Same Tower
Analysis on Influence of Different Aluminum Sheath Structure on Electrical Characteristics of Cable
Development and Project Application of Live Ice-melting System for UHVDC Transmission Lines
Characterization of Short-circuit Fault Voltage Distribution on Load Side of Cable-GIL Hybrid System
Related Author
LE Yanjie
GAO Zhen
LIU Zongxi
SHEN Qi
SUN Lu
CAI Yong
CONG Yun
PENG Zhaowei
Related Institution
China Electric Power Research Institute Co., Ltd.
Zhejiang Zhoushan Marine Power Research Institute Co., Ltd.
State Grid Zhejiang Electric Power Co., Ltd.
State Grid Zhoushan Electric Power Supply Company of Zhejiang Power Corporation
Beijing Power Transmission and Transformation Co., Ltd.