Study on the Application of On-line Diagnosis Method for Inter-turn Insulation of Dry-type Air-core Reactor Based on Wireless Hot Spot Temperature Measurement
|更新时间:2025-04-26
|
Study on the Application of On-line Diagnosis Method for Inter-turn Insulation of Dry-type Air-core Reactor Based on Wireless Hot Spot Temperature Measurement
High VoltageApparatusVol. 56, Issue 2, Pages: 215-220(2020)
HUO Feng, DUAN Changjun, ZHOU Guangdong, et al. Study on the Application of On-line Diagnosis Method for Inter-turn Insulation of Dry-type Air-core Reactor Based on Wireless Hot Spot Temperature Measurement[J]. High voltageapparatus, 2020, 56(2): 215-220.
HUO Feng, DUAN Changjun, ZHOU Guangdong, et al. Study on the Application of On-line Diagnosis Method for Inter-turn Insulation of Dry-type Air-core Reactor Based on Wireless Hot Spot Temperature Measurement[J]. High voltageapparatus, 2020, 56(2): 215-220. DOI: 10.13296/j.1001-1609.hva.2020.02.032.
Study on the Application of On-line Diagnosis Method for Inter-turn Insulation of Dry-type Air-core Reactor Based on Wireless Hot Spot Temperature Measurement
This paper reviews the various testing methods and applications for the inter-turn insulation of dry-type air-core reactor by domestic research and technicians.According to the temperature rise effect in the fault process of dry-type reactor
the diagnosis method of inter-turn insulation defect of dry-type air-core reactor based on temperature rise distribution is proposed.lt is proved that the method is effective by making a temperature-rise prototype and simulating calculation model
carrying out simulation calculation and testing model.This method is validated by the test
disintegration and operation of the back-running reactor
which is applicab le to the operation state diagnosis of dry reactor and the real-time monitoring of the operation state of the important dry reactor in the field conditions.