ZHANG Qun, ZHAO Qian, HAO Junfang, et al. Study on Fault Isolation Strategy of Overhead Transmission Line Based on DC Circuit Breaker in Flexible DC Grid[J]. High voltageapparatus, 2020, 56(3): 17-22.
ZHANG Qun, ZHAO Qian, HAO Junfang, et al. Study on Fault Isolation Strategy of Overhead Transmission Line Based on DC Circuit Breaker in Flexible DC Grid[J]. High voltageapparatus, 2020, 56(3): 17-22. DOI: 10.13296/j.1001-1609.hva.2020.03.003.
Study on Fault Isolation Strategy of Overhead Transmission Line Based on DC Circuit Breaker in Flexible DC Grid
Flexible HVDC technology will develop into flexible HVDC power grid with different topologies in the future.Considering the economy and commonality
the flexible HVDC grid using overhead line will be the development trend of the future.But the fault rate of overhead line is high
how to quickly isolate the DC line fault and restore the system to normal operation without affecting the power transmission is a key factor restricting the development of flexible HVDC power grid.Against this problem
based on Zhangbei flexible DC power grid demonstration project
the half-bridge modular multilevel converter has been studied in this paper
and DC overhead line fault isolation strategy and overhead line fault recovery strategy for engineering application have been proposed.Based on RTLAB real-time simulation platform
a four-terminal DC grid system of Zhangbei project is set up.The corresponding fault isolation strategy and fault recovery strategy are simulated.The results show that the impact of DC line faults on the AC system can be reduced
and the effect of the DC current limit removal on system stability and safety can be reduced
providing a reference for flexible HVDC power grid project application.