WU Tian, YANG Dong, LI Peng, et al. Study on the Model Simpliflcation Method for the Calculation of Arc Pressure Rise in MV Switchgear[J]. High voltageapparatus, 2020, 56(3): 39-45+53.
WU Tian, YANG Dong, LI Peng, et al. Study on the Model Simpliflcation Method for the Calculation of Arc Pressure Rise in MV Switchgear[J]. High voltageapparatus, 2020, 56(3): 39-45+53. DOI: 10.13296/j.1001-1609.hva.2020.03.006.
Study on the Model Simpliflcation Method for the Calculation of Arc Pressure Rise in MV Switchgear
The arcing fault inside medium-voltage(MV) switchgear happened occasionally.The great energy is released in a short time in the switchgear
resulting in pressure rise rapidly
which caused a serious threat to the safety of the equipment
buildings and personnel.Based on the simplified principles such as regularization replacement of the parts and isovolumetric replacement of the compartment
the simplified methods for the switchgear complex model are proposed in the paper.The pressure distribution for the different simplified models are calculated by the CFD
and the best simplified method for the model is given.The results are calculated by the pressure rise standard calculation method(SCM) and CFD
and the difference of both is analyzed.The results show that the model obtained by combined with the regularization replacement of the parts and the isovolumetric replacement of the compartment can get similar results with the original model
and the computation time is reduced by 54.39%.After the pressure relief cover is open
the pressure distribution has a great difference in the compartment.The result error is big by using SMC
Pressure Rise Calculation and Pressure Relief Efficiency Analysis in the Cable Room of Switchgear Due to Internal Short-circuit Explosion
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Research on the Influence of Temperature and Humidity on the Physical Signal of Partial Discharge of Switchgear
RESEARCH ON THE CHARACTERISTICS OF ULTRASONIC SIGNALS OF PARTIAL DISCHARGE IN 12V SWITCHGEAR CABINET
A Microcontroller-based Protection Unit for Switchgear of Terminal Users
Related Author
黎子晋
方蓓贝
黎鹏
肖盼
吴田
普子恒
JI Hongquan
XIN Feng
Related Institution
China Three Gorges University
湖北省输电线路工程技术研究中心(三峡大学)
State Grid Beijing Electric Power Company Urban Power Supply Company
State Grid Beijingg Electric Power Company
Power Research Institute of State Grid Beijing Electric Power Co., Ltd.