WANG Gang, PENG Yanqing, ZHUANG Zhijian, et al. Method to Diagnose the Concentricity of Tulip Contacts of a Medium Voltage Circuit Breaker Handcart Based on the Armature Current of a BLDCM[J]. High voltageapparatus, 2020, 56(3): 46-53.
WANG Gang, PENG Yanqing, ZHUANG Zhijian, et al. Method to Diagnose the Concentricity of Tulip Contacts of a Medium Voltage Circuit Breaker Handcart Based on the Armature Current of a BLDCM[J]. High voltageapparatus, 2020, 56(3): 46-53. DOI: 10.13296/j.1001-1609.hva.2020.03.007.
Method to Diagnose the Concentricity of Tulip Contacts of a Medium Voltage Circuit Breaker Handcart Based on the Armature Current of a BLDCM
there is no method for high voltage withdrawable switchgears to determine whether the concentricity of the tulip contacts of a circuit breaker handcart is good.This paper used a brushless DC motor as the driving motor for the circuit breaker handcart
and a method to diagnosis the concentricity of the tulip contacts of a medium voltage circuit breaker handcart was proposed.First of all
the mathematic model of the brushless DC motor was analyzed to determine the influencing factor of armature current.Static contacts with different eccentric distances were used to replace the original static contacts of the test bed to simulate different degrees of center deviation.Secondly
the current curves were processed by mean filter and Gauss fitting
and the parameter of the fitting function including A
xmax and the mean current of the meshing stage were extracted as the curves characteristics.The characteristics was used to train a BP neural network which was used to diagnosis the concentricity of tulip contacts.Finally
more data was sampled to test the method.It has been proved that the method was able to recognize different degrees of center deviation
and the method is high accuracy.It can provide a new idea to diagnosis the concentricity of tulip contacts of a medium voltage circuit breaker handcart.