SONG Ping, LU Qiyu, ZHANG Qiqi, et al. Combined Intrusive PD Detection Technology with UHF and AE Methods for Transformer[J]. High voltageapparatus, 2020, 56(3): 67-71.
SONG Ping, LU Qiyu, ZHANG Qiqi, et al. Combined Intrusive PD Detection Technology with UHF and AE Methods for Transformer[J]. High voltageapparatus, 2020, 56(3): 67-71. DOI: 10.13296/j.1001-1609.hva.2020.03.010.
Combined Intrusive PD Detection Technology with UHF and AE Methods for Transformer
In the latest international standard IEC TS 62478-2016 "High voltage test techiques-measurement of partial discharges by electromagnetic and acoustic methods"
it is pointed out that the existing external ultrasonic method for PD measurement mainly exists in the attenuation of acoustic wave from the equipment shell and the multipath transmission problem caused by acoustic impedance of different media.Based on the structure of transformer oil valve
the UHF antenna and piezoelectric ceramic acoustic emission(AE) sensor are integrated.Considering the coupling of electromagnetic and ultrasonic signals and the leakage prevention of transformer oil
an intrusive PD composite sensor capable of simultaneously coupling UHF and AE signals is developed.The comparison test with a110 kV transformer between the built-in composite sensor and the external piezoelectric ceramic AE sensor shows that the designed PD composite sensor can effectively measure the UHF and AE signals with a certain time difference At from weak discharges in oil
which provides a new"acoustic-electrical" combined detection technology for PD in tran sformer.