Electric Field Calculation of Composite Hollow Insulator with Strong Wind Reflection
The composite hollow insulator has a length of about 8~10 m
and the elastic modulus is less than porcelain insulator.The strong wind deflects the composite hollow insulator
where the wind deflection is affected by the wind speed and the elastic modulus under the working situation.Whether the large wind deflection will cause the distortion of the electric field strength inside and outside the composite hollow insulator
is rarely studied.Due to the high cost and fewer returned samples
in this paper
finite element analysis method is used to simulate the electric field the strong wind conditions.According to the first order modal vibration mode of the composite hollow insulator of 750 kV
the electric field in the critical region of the insulation is calculated.It is clarified that the wind reflection can cause severe distortion of the electric field near the grounding shield electrode.This paper points out that in the strong wind area
the wind speed
the working temperature of the FRP pipe and the wind reflection of the composite hollow insulator should be monitored.