LI Zhiqi, LUO Richeng, LI Wen, et al. Analysis of Potential Shift Characteristics of Live Working on ±800 kV UHVDC Transmission Line[J]. High voltageapparatus, 2020, 56(3): 164-168+175.
LI Zhiqi, LUO Richeng, LI Wen, et al. Analysis of Potential Shift Characteristics of Live Working on ±800 kV UHVDC Transmission Line[J]. High voltageapparatus, 2020, 56(3): 164-168+175. DOI: 10.13296/j.1001-1609.hva.2020.03.024.
Analysis of Potential Shift Characteristics of Live Working on ±800 kV UHVDC Transmission Line
In order to ensure the safety of workers while live working on±800 kV transmission line
the analysis of the potential transfer characteristics is helpful to take appropriate safety protection for operating personnel.By establishing the model of the rod-plate gap discharge based on hydrodynamics theory during the process of potential transfer
the electric field intensity of the air gap between the worker and the transmission lines is acquired
the transient energy during potential shift is calculated
and the value of potential transfer energy distribution characteristics is analyzed while the transfer distance changed from 0.3 m to 0.6 m.The results show that the transfer energy under different transfer distances is around 1.0 J
and the transfer energy increases with the increase of transfer distance.When the transfer energy is higher than 1.0 J the conductive gloves have the risk of being ablated.Thus
to protect the operating personnel
a potential
transfer rod is required when transferring to the live conductor of the±800 kV transmission line.
Simulation Analysis of Electric Field on Live Working of ±800 kV Transmission Line
Research on Human Digital Twins for Live Working on Transmission Lines Based on Attitude Estimation
Study on Distribution of Decay-like Fracture of Composite Insulator
Study on the Amplitude and Energy Characteristics of the in and out of Equipotential Pulse Current for 1000 kV Transmission Line Tension Tower Based on HHT
Live Working Insulation Blanket Surface Defect Recognition Based on Improved YOLOv8
Related Author
PAN Junwen
LUO Richeng
PAN Qianwen
ZHANG Chengwu
XU Jinshuai
WANG Wei
MA Aiqing
GAO Chao
Related Institution
Suizhou Power Supply Company,State Grid Hubei Electric Power Company
School of Electrical and information Engineering, Changsha University of Science & Technology
School of Electrical Engineering, Shanghai University of Electric Power
Tsinghua Shenzhen International Graduate School
Henan Key Laboratory of Power Transmission Line Galloping Prevention and Control Technology, State Grid Henan Electric Power Research Institute