ZHENG Zongan. Research and Application of Fault Detection of Reactor Turn-to-turn Short Circuit Based on Magnetic Field Detection Method[J]. High voltageapparatus, 2020, 56(3): 217-223.
ZHENG Zongan. Research and Application of Fault Detection of Reactor Turn-to-turn Short Circuit Based on Magnetic Field Detection Method[J]. High voltageapparatus, 2020, 56(3): 217-223. DOI: 10.13296/j.1001-1609.hva.2020.03.032.
Research and Application of Fault Detection of Reactor Turn-to-turn Short Circuit Based on Magnetic Field Detection Method
The probability of short circuit faults in dry-type air-core reactor is extremely high
there are always huge adverse effects if not eliminated in time.However
there exist low accuracy and sensitivity with the traditional fault detection method when detecting the early failure or minor turn-to-turn short circuit faults in dry-type air-core reactor.This paper proposes a fault detection method of turn-to-turn short circuit of dry-type air-core reactor based on magnetic field detection method.Firstly
the sampled data are smoothed by using the sliding mean method.Then
the turn-to-turn failure can be determined according to the error limit of the control model.In this way
the online monitoring and early warning of the turn-to-turn short circuit fault is realized timely in the initial and developing period
with high accuracy.Engineering verification shows that the signal intensity can be increased by 50-100 times with the proposed method compared to traditional method
and proposed method performs good reliability and stability.The method proposed is able to be applied in the engineering application and expected widespread applications in power systems.