Shaking Table Test and Numerical Analysis on 1 100 kV Column Circuit Breaker
In order to investigate the seismic performance of 1 100 kV column circuit breaker under the action of seismic wave
according to the seismic test method of UHV electrical equipment
the shaking table test of earthquake simulation is carried out
and the numerical analysis of the structure is carried out by using the finite element software.The equipment frequency
and some key parts’ strain and acceleration are measured through white noise sweep and artificial standard time history wave seismic test.The test results show that the maximum stress of the composite pillar casing is 38.58 MPa under the action of 0.4 g seismic wave
which is lower than the rated mechanical load stress of the composite material.Maximum strain occurs at the pillar casing roots;it is vulnerable parts of the circuit breaker equipment.The strong seismic wave could change the dynamic performance of the structure;the structure presents obvious nonlinear characteristics.According to the experimental data
the damping value of the structure is obtained and gives it to the numerical model.The simulation results are in good agreement with the test results
and the maximum error is 10.30%.The nonlinear characteristics of structural damping with the change of the input seismic wave intensity should be taken into account in the simulation calculation.