LIU Fei, DAI Tongling, WANG Na. Development of 1 100 kV GIL Gas Barrier Insulator[J]. High voltageapparatus, 2020, 56(4): 23-28. DOI: 10.13296/j.1001-1609.hva.2020.04.004.
gas barrier insulator plays the key roles of separating gas compartments and providing a contamination barrier and insulation to the ground.It is very important to develop reliable 1 100 kV GIL gas barrier to ensure the safe service of 1 100 kV GIL.Applying finite element software
its dielectric performance and mechanical performance are computed
results show:through the optimization of its insulation design
remove the grounding shield ring can effectively reduce the electric field strength in the triple zone;the cone is completely surrounded by a particle trap which is electrically bonded to the enclosure
in order to trap particles moving under the influence of gravity.The 1 100 kV spacer passed its type test successfully in High Voltage Apparatus Quality Test & Research Center
its lightning pulse withstand voltage reaches 2 400 kV and its burst pressure reaches 3.45 MPa
showing that its dielectric performance and mechanical performance have a larger margin.