ZHENG Yiming, LIU Shi, LIU Haojun, et al. Closing Switching Overvoltage Analysis of 220 kV Power Cable Transmission Lines[J]. High voltageapparatus, 2020, 56(4): 153-158.
ZHENG Yiming, LIU Shi, LIU Haojun, et al. Closing Switching Overvoltage Analysis of 220 kV Power Cable Transmission Lines[J]. High voltageapparatus, 2020, 56(4): 153-158. DOI: 10.13296/j.1001-1609.hva.2020.04.024.
Closing Switching Overvoltage Analysis of 220 kV Power Cable Transmission Lines
Two sets of longitudinal protections tripped after a 220 kV cable line was closed by one side circuit breaker with the disconnection of the other side circuit breaker.It was found by inspection that the connector of C phase power cable was broken down.In order to investigate the closing overvoltage of the power cables and analyze the cause of this breakdown
the repaired cable line was tested in line with the accident status
and the voltage and current in the switching process were monitored.At the same time
considering the overvoltage that may exist in the cable along the line during the no-load switching
the electromagnetic transient calculation program PSCAD was adopted to simulate and analyze the overvoltage of the cable.Finally
according to the measured and simulation results
the operation and maintenance countermeasures were put forward.