JU Zeli, ZHU Yao, PU Lu, et al. Study on the Voltage Integrated Compensation Method of Distribution Network[J]. High voltageapparatus, 2020, 56(4): 235-240.
JU Zeli, ZHU Yao, PU Lu, et al. Study on the Voltage Integrated Compensation Method of Distribution Network[J]. High voltageapparatus, 2020, 56(4): 235-240. DOI: 10.13296/j.1001-1609.hva.2020.04.037.
Study on the Voltage Integrated Compensation Method of Distribution Network
it is emphasized that the deviation of the amplitude of voltage in three-phase powersupply system
including 10 kV and the lowers
must be smaller than ±7%.As for long-distance radical distribution circuits that connect with heavy loads and have low power factor
voltage amplitude will be below the limit
9.3 kV.Kinds of measures can be taken to compensate voltage
such as installing series compensation and shunt compensating device
or adopting off-load-tap-changing transformer and on-load-tap-changing transformer.For the circuits at the end of which voltage amplitude drops much
it’ s necessary to adopt several measures simultaneously to satisfy the requirement of national standard.Taking a typical 10 kV radial distribution circuits for example
the paper adopts EMTP-ATP software to simulate the voltage compensation effect of series compensation device
shunt compensation device and transformer voltage regulation on the line during system steady operating.An effective integrated voltage-regulating scheme is presented to improve the voltage loss along the line.