ZHAO Ke, LU Dongsheng, LU Yangze, et al. Calculation and Analysis of Transient Temperature Field of Vehicle-mounted Oil-immersed Air-core Reactor[J]. High voltageapparatus, 2020, 56(5): 69-73+78.
ZHAO Ke, LU Dongsheng, LU Yangze, et al. Calculation and Analysis of Transient Temperature Field of Vehicle-mounted Oil-immersed Air-core Reactor[J]. High voltageapparatus, 2020, 56(5): 69-73+78. DOI: 10.13296/j.1001-1609.hva.2020.05.011.
Calculation and Analysis of Transient Temperature Field of Vehicle-mounted Oil-immersed Air-core Reactor
The current and the heating power of vehicle-mounted oil-immersed air-core reactor are high in GIL AC voltage withstand test.To avoid overheat fault
it is necessary to analyze the transient temperature field of vehiclemounted oil-immersed air-cored reactor.In this paper
the finite element method is applied to calculate the transient temperature filed of the reactor and the flow field of the oil
and the temperature rise and heat dissipation property of the reactor are analyzed.The heat dissipation rate of the reactor through natural convection of insulating oil is limited.The effects of two auxiliary cooling measures are calculated.The external blowing measure is easy to implementbut its cooling effect is unsatisfactory.The ambient temperature reduction measure is not difficult to implement
and its cooling effect is better than that of the external blowing measure.The calculation in this paper may be taken as a reference for UHV GIL voltage withstand test.