LIU Tong, CHEN Songtao, LU Yangze, et al. Calculation of Power-frequency Magnetic Filed for Vehicle-mounted Oil-immersed Air-cored Reactor[J]. High voltageapparatus, 2020, 56(5): 74-78.
LIU Tong, CHEN Songtao, LU Yangze, et al. Calculation of Power-frequency Magnetic Filed for Vehicle-mounted Oil-immersed Air-cored Reactor[J]. High voltageapparatus, 2020, 56(5): 74-78. DOI: 10.13296/j.1001-1609.hva.2020.05.012.
Calculation of Power-frequency Magnetic Filed for Vehicle-mounted Oil-immersed Air-cored Reactor
The vehicle-mounted oil-immersed air-cored reactor has no core
and strong magnetic field may occur during UHV GIL voltage withstand test.To investigate the magnetic flux density around the reactor
a circuit model of the reactor is set up and the power-frequency magnetic flux density around the reactor is calculated based on the BiotSavar’s law.The calculation result is equal to the result of finite element method.The proposed algorithm has lower requirement for computer performance and faster computation speed
compared with the finite element method.The obtained power-frequency magnetic flux density distribution around the reactor may be taken as reference in formulation of safety regulation for UHV GIL voltage withstand test.