CAO Xiaobin, CHEN You, TANG Ping, et al. Insulator String Conductance Distribution Model of ±800 kV DC Transmission Line and Its Influence on the Voltage and Leakage Current[J]. High voltageapparatus, 2020, 56(5): 86-93.
CAO Xiaobin, CHEN You, TANG Ping, et al. Insulator String Conductance Distribution Model of ±800 kV DC Transmission Line and Its Influence on the Voltage and Leakage Current[J]. High voltageapparatus, 2020, 56(5): 86-93. DOI: 10.13296/j.1001-1609.hva.2020.05.014.
Insulator String Conductance Distribution Model of ±800 kV DC Transmission Line and Its Influence on the Voltage and Leakage Current
To analyze the composition and distribution characteristics of the leakage current in the insulator fittings in different positions of a DC insulator string
we established a three-dimensional finite element model of DC insulator string
calculated the mutual conductance of insulator fittings to transmission line and ground
and analyzed the influencing factors and distribution characteristics of the leakage current.The results show that there is a great difference of leakage current in insulator fittings between different positions on the DC insulator string.The leakage current in insulator fittings consists of three parts—the first part flows from insulator fittings through air to ground
the second part flows from transmission line through air to insulator fittings
and the third part flows along the surface of insulator.The voltage distribution of the DC insulator string is in a dynamic equilibrium state produced by both distributed capacitance and distributed conductance.The study may provide reference for the research on corrosion of insulator hardware