XU Yang, ZHOU Dianbo, DING Dengwei, et al. Detection of Partial Discharge Induced by Surface Defect of GIS Basin Insulators[J]. High voltageapparatus, 2020, 56(5): 101-106.
For the purpose of defect state monitoring and diagnosis of the basin insulators in GIS
experiment is carried out on a basin insulator with surface defects
and the characteristics of partial discharge(PD) are detected and compared with that of an eligible insulator.Moreover
the experimental results are verified with the results of photoelectric effect-based PD detecting method
and the correlation between the optical intensity and the frequency of the PD pulses is obtained on the basis of the analysis on the experimental data.This research may be beneficial to the onsite detection and recognition of the surface defects on GIS basin insulators
as well as to the improvement of the manufacturing technique of GIS insulators.