ZHANG Xicheng, LIN Xin, LI Hui, et al. Design and Numerical Calculation of Waste Heat Utilization Unit for Power Transmission Pipeline[J]. High voltageapparatus, 2020, 56(5): 149-154.
ZHANG Xicheng, LIN Xin, LI Hui, et al. Design and Numerical Calculation of Waste Heat Utilization Unit for Power Transmission Pipeline[J]. High voltageapparatus, 2020, 56(5): 149-154. DOI: 10.13296/j.1001-1609.hva.2020.05.023.
Design and Numerical Calculation of Waste Heat Utilization Unit for Power Transmission Pipeline
In new type of power transmission pipeline conductor produces heat due to electrical loss.To make use of the waste heat for heating of building via heat-conducting medium
a waste heat utilization unit for power transmission pipeline is designed in this study under the premises that the normal operation of the transmission pipeline is not been affected
the insulation strength of the unit is assured
and the connection to the transmission line is convenient.The structure of the unit
the function of each component
and the unit’s working principle and connection to the transmission pipeline are described.In order to understand the insulation and temperature rise of the waste heat utilization unite
a corresponding model of the unit is established.The model’s electric field and temperature field are calculated and analyzed
and the results show that the maximum electric field strength of the unit insulation is 1.86 kV/mm
which is far less than the dielectric strength of the insulating medium;and the temperature of the heat exchange layer in the unnit in the range of 60~80℃