On-site Treatment and Data Analysis of Excessive Gas Content in Electrical Equipment
The power transformers and reactors are the core equipment of the power system.It is of great significance to study effective methods to evaluate the internal early fault status to ensure the reliable operation of equipment.Among them
the dissolved gas content in transformer oil which can promptly reflect the sealing performance has become the main technology for maintenance and fault diagnosis of oil-immersed power equipment.Based on the three typical failure cases of excessive gas content in transformer oil in Fujian Province
this paper analyzes the reasons and the treatment basis for the excessive gas content through the on-site leakage point check by power cut work and the comparison of the historical gas content
s and O
2
/N
2
ratios.For the first time
this paper establishes a method for judging the sealing performance of oil-immersed high-voltage equipment by using gas content and O
2
/N
2
ratio historical curves
which can provide an important reference for operation and maintenance of equipment with excessive gas content.