Mechanical Condition Detection of Vacuum On-load Tap-changer for Converter Transformer Based on Time-frequency Domain Characteristics of Vibration Signal
|更新时间:2025-04-26
|
Mechanical Condition Detection of Vacuum On-load Tap-changer for Converter Transformer Based on Time-frequency Domain Characteristics of Vibration Signal
High VoltageApparatusVol. 56, Issue 6, Pages: 232-237(2020)
PAN Zhicheng, ZHANG Jinyin, ZHOU Haibin, et al. Mechanical Condition Detection of Vacuum On-load Tap-changer for Converter Transformer Based on Time-frequency Domain Characteristics of Vibration Signal[J]. High voltageapparatus, 2020, 56(6): 232-237.
PAN Zhicheng, ZHANG Jinyin, ZHOU Haibin, et al. Mechanical Condition Detection of Vacuum On-load Tap-changer for Converter Transformer Based on Time-frequency Domain Characteristics of Vibration Signal[J]. High voltageapparatus, 2020, 56(6): 232-237. DOI: 10.13296/j.1001-1609.hva.2020.06.033.
Mechanical Condition Detection of Vacuum On-load Tap-changer for Converter Transformer Based on Time-frequency Domain Characteristics of Vibration Signal
according to the structural characteristics of vacuum on-load tap-changer for converter trans-former
vibration test is carried out during switching process in the field. Vibration characteristics in the time domainand frequency domain are studied. Based on the time-frequency domain characteristics of the vibration signal
amethod to detect the condition of vacuum on-load tap-changer(OLTC)for converter transformer is proposed
and itsengineering validity is verified. This method is proved to be effectively detect mechanical defects of vacuum on-loadtap-changer
such as abnormal motor-drive mechanism
broken support plate and cracked absorber support.