Field Application of Power Transformer Oscillating Switching Impulse Voltage Withstand Test and Diagnosis Technology
适合在设备交接及大修后在现场进行冲击电压试验时采用。文中在现场对一台110 k V主变C相绕组进行振荡操作冲击耐压试验
通过高、低压电压波形、中性点电流波形和传递函数等参量对变压器进行综合故障诊断。研究发现
电压电流波形在波尾时间之前的部分无明显差异
此后由于励磁电感发生饱和
电压、电流波形发生变化
且试验电压越高
励磁电感饱和的影响越明显。电压传递函数在高电压下极值点频率增大
而电流传递函数则无明显变化
说明缺陷位于变压器C相低压绕组
与绕组变形等常规试验结果一致
验证了振荡操作冲击诊断技术的有效性。
Abstract
Oscillating impulse voltage waveform has the advantages of high efficiency
suitable for field use andclose to the actual waveform of equipment. It is suitable for field impulse voltage test after equipment handover andoverhaul. In this paper
a 110 k V transformer C-phase winding is tested for oscillating switching impulse voltage.The transformer fault diagnosis is carried out by high and low voltage waveform
neutral current waveform and trans-fer function. It is found that the waveforms of voltage and current have no significant difference before the wave-tailtime. The waveforms of voltage and current changes due to the saturation of magnetizing inductance
which is obvi-ous at high voltage
and the higher the test voltage is
the more obvious the influence of excitation inductance satura-tion is. The peak frequency of voltage transfer function increases at high voltage
while the current transfer functiondoes not change significantly. It shows that the defect is located in the C phase low voltage winding of the transform-er
which is consistent with the conventional test results. The validity of the oscillation switching impulse diagnosistechnology is verified.