NIU Bo, MA Feiyue, DING Pei, et al. Fault Analysis of Pre-insertion Resistors for 800 kV Circuit Breakers in AC Filters Field[J]. High voltageapparatus, 2020, 56(7): 36-43.
NIU Bo, MA Feiyue, DING Pei, et al. Fault Analysis of Pre-insertion Resistors for 800 kV Circuit Breakers in AC Filters Field[J]. High voltageapparatus, 2020, 56(7): 36-43. DOI: 10.13296/j.1001-1609.hva.2020.07.006.
Fault Analysis of Pre-insertion Resistors for 800 kV Circuit Breakers in AC Filters Field
Pre-insertion resistors(PIR)are used to suppress the closing inrush current or the operating overvoltageduring the closing of the circuit breakers. It is mainly used in the AC filter field of converter stations and transmissionlines with rated voltage 800 kV and above. Its special application environment causes its failure rate to be relativelyhigh than other electrical components. Through the transient waveform analysis
acoustic vibration signal detection
physical field simulation and other methods during the closing process of the circuit breaker
the abnormal operationof the circuit breaker caused by the defect of the PIR is analyzed
and the reasons for the abnormal PIR are given.The correctness of the analysis method is verified by returning to the factory for disassembly. Finally
correspondingimprovement measures were proposed for the potential defects of the series PIR and the shunt PIR to avoid air gapbreakdown during the operation of the circuit breaker.