Research on the Characteristics and Mechanism of Partial Discharge of Internal Crevice in GIS Insulator
The crack inside the GIS insulator is a common insulation defect. However
most of the researches on the characteristics and mechanism of the partial discharge(PD)of it are based on the artificial defect made in the laboratory
rather than the cracks found on practical insulators
and thus
the results of those investigations are inevitably inaccurate compared with the practical situation in substations. In this paper
a GIS post insulator with crack inside is introduced to study its PD characteristics under short term and long term high voltage
and the mechanism and process of the discharge is explained using the dielectric barrier discharge(DBD)model. The characteristics derived from the theoretical analysis are compared with those obtained in the PD experiment to demonstrate the validity of the analysis
and the reason why the discharge is unable to be detected by the ultra-high frequency(UHF)method is explained. The research contents in this paper will make significant sense on the improvement of the manufacturingtechnique and the selection of the detecting method in delivery test and on-site measurement.