Research on Voltage Distribution of 252 kV GIS with Double Isolation Break for Uninterrupted Power Supply Expansion
In order to meet the requirements of expansion break with high insulation margin for uninterrupted power supply during GIS expansion butt joint and on-site withstand voltage
this paper introduces a 252 kV GIS uninterrupted expansion equipment with double isolation breaker
which uses two isolation breakers in series to form expansion breaker. Due to the influence of the equivalent capacitance of the breaker and the stray capacitance to the ground
the voltage ratio of the two breakers is not 1:1. In order to verify the insulation performance of the double isolation breaker
the maximum withstand voltage of the expansion breaker is analyzed first
establishes the equivalent circuit analysis model to derive the theoretical formula
then the Ansys finite element software is used as the calculation tool
and then the research and analysis method combining theoretical formula derivation and simulate calculation is used to obtain the breaker voltage distribution. The results show that
the high-voltage side is olation breaker voltage issignificantly higher than the low-voltage side. for the three-phase common box structure
the three-phase breaker voltage division ratio is slightly different
and the middle phase division voltage ratio is slightly lower. According to the calculation results
evaluate the insulation performance of the double isolated breaker