LIAO Haoquan, WU Zhiying, RAO Hongjiang, et al. Measurement Scheme of Insulation Resistance of Power Transformer Based on Nonlinear Error Current Suppression Algorithm[J]. High voltageapparatus, 2020, 56(7): 189-192.
LIAO Haoquan, WU Zhiying, RAO Hongjiang, et al. Measurement Scheme of Insulation Resistance of Power Transformer Based on Nonlinear Error Current Suppression Algorithm[J]. High voltageapparatus, 2020, 56(7): 189-192. DOI: 10.13296/j.1001-1609.hva.2020.07.027.
Measurement Scheme of Insulation Resistance of Power Transformer Based on Nonlinear Error Current Suppression Algorithm
The polarization process of insulation dielectric of transformer is slow
and it takes a long time to measure the stable insulation resistance. In order to shorten the measurement time
a parameter estimation measurement method of insulation resistance is studied in this paper. Firstly
the extended Debye model of oil-paper insulation is established. Based on the polarization/depolarization current test
the depolarization current parameters are estimated by matrix pencil algorithm
and get the insulation resistance after dielectric polarization stabilization.The experiment results show that the error caused by absorption current can be eliminated. Meanwhile
shortened the measurement time of insulation resistance.