Calculation and Analysis of Steady Electric Field of Vehicle-mounted Oil-immersed Air-cored Reactor
Rated voltage of vehicle-mounted oil-immersed air-cored reactor is up to 1 100 kV.To ensure the safety during operation
the steady electric field of vehicle-mounted oil-immersed air-cored reactor is analyzed.In this paper
a simplified finite element model of vehicle-mounted oil-immersed air-cored reactor is created and the correctness of this model is verified.According to the electric field calculation result
the insulation oil in the reactor is very important to avoid discharge.The geometry of the epoxy resin shell should be set reasonably to reduce the electric field strength caused by dielectric polarization.By applying the shielding ball
the peak of electric field strength is reduced by 73.12%.The risk of discharge reduces and the dielectric aging caused by high electric field strength is avoided.