CAI Mengyi, ZHAO Hengyang, YANG Wei, et al. Electric Field Analysis and Shielding Plate Structure Optimization for Bushing in 40.5 kV Switchgear Cabinet[J]. High voltageapparatus, 2020, 56(10): 13-17+22.
CAI Mengyi, ZHAO Hengyang, YANG Wei, et al. Electric Field Analysis and Shielding Plate Structure Optimization for Bushing in 40.5 kV Switchgear Cabinet[J]. High voltageapparatus, 2020, 56(10): 13-17+22. DOI: 10.13296/j.1001-1609.hva.2020.10.003.
Electric Field Analysis and Shielding Plate Structure Optimization for Bushing in 40.5 kV Switchgear Cabinet
the 40.5 kV cabinet bushing with tipical double shield structure has been taken as the research object
the computation model of bus room in 40.5 kV gas insulated switchgear cabinet has been established by using 3D finite element analysis sofeware.The influence from cabinet shell
busbar
contact box
post insulator and metal partition that on the potential and electric field distribution of cabinet bushing has been considered.The potential and electric field distribution of 40.5 kV cabinet bushing has been computed.The electric field distribution regularity of cabinet bushing with double shield structure has been analyzed by electric field analytical method.A reasonable scheme of double shield structure for cabinet bushing has been put forward
which could effectively improve the electric field distribution inside the cabinet bushing.The research results of this paper improve the insulation level of the bushing through the cabinet
effectively solve the problem of insufficient local insulation capacity of the bushing through the cabinet in the bus room of the switchgear
and improve the operation reliability of the equipment.