LI Xu, YANG Dingge, SHANG Yu, et al. Research on the Influence of Different Aging Conditions on the Insulation Performance of Insulation in Switchgear[J]. High voltageapparatus, 2020, 56(10): 48-55.
LI Xu, YANG Dingge, SHANG Yu, et al. Research on the Influence of Different Aging Conditions on the Insulation Performance of Insulation in Switchgear[J]. High voltageapparatus, 2020, 56(10): 48-55. DOI: 10.13296/j.1001-1609.hva.2020.10.009.
Research on the Influence of Different Aging Conditions on the Insulation Performance of Insulation in Switchgear
Switchgear is an important power equipment in power system.The insulation components in the switchgear will be affected by different aging conditions(pollution aging
moisture condensation aging
cold and hot cycle aging
thermal aging
etc.) under actual working conditions.In order to explore the influence of different aging conditions on the insulation performance of switchgear insulation parts
based on the actual operating conditions of the switchgear
a comprehensive consideration of the influence process of the conductive circuit heating
moisture and condensation
cold and hot circulation
pollution and other factors on the performance of the insulation aging in the switchgear.The influence process of insulation performance aging of switchgear caused by conductive circuit heating
moisture and condensation
cold and hot circulation
pollution and other factors is comprehensively considered.By carrying out simulation tests under different combinations of factors
the partial discharge and withstand voltage
of the insulation under different aging conditions are tested to assess the impact of various aging factors on the insulation performance of the switchgear.The experimental results show that the dirty aging which reduces the halo and extinction voltage of the insulator can also reduce the withstand voltage of the insulator.The more serious the dirty aging is
the more obvious declinating of the insulator’ s withstand voltage is.With consideration of the moisture condensation aging
the halo and extinguishing voltage of the insulator will be greatly reduced
as well as the partial discharge value will be greatly increased.If further considering the thermal aging
the halo and extinguishing voltage of the insulator is further weakened.Meanwhile
the thermal aging can reduce the halo voltage and extinction voltage of the bushing and contact box
and slightly reduce the withstand voltage performance.
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Study on Compatibility of Vegetable Oil and Solid Insulation Materials in Power Transformer
Research on the Influence of Temperature and Humidity on the Physical Signal of Partial Discharge of Switchgear
RESEARCH ON THE CHARACTERISTICS OF ULTRASONIC SIGNALS OF PARTIAL DISCHARGE IN 12V SWITCHGEAR CABINET
A Microcontroller-based Protection Unit for Switchgear of Terminal Users
Related Author
JI Hongquan
XIN Feng
LIU Ruoxi
WANG Zhihui
LUO Zhongge
GUI Yuan
LIANG Suning
YANG Zhi
Related Institution
Power Research Institute of State Grid Beijing Electric Power Co., Ltd.
State Grid Beijingg Electric Power Company
State Grid Beijing Electric Power Company Urban Power Supply Company
State Grid Zhejiang Electric Power Research Institute
State Key Laboratory of Power Transmission Equipment & System Security and New Technology, School of Electrical Engineering, Chongqing University