Discussion on Insulation Performance of 40.5 kV Air-insulated Switchgear
40.5 kV air-insulated switchgear is taken as the research object
and its insulation characteristics are explored. First
the electric field simulation calculation of air-insulated switchgear is analyzed. Second
based on the electric field simulation
the insulating rod shed and pole shed of the circuit breaker in the air-insulated switchgear are improved and optimized. The results show that the single improvement of the shed of insulated pull rod has the best optimization effect
the field strength distribution is obviously improved
the final field strength is decreased by 16.7%
and the operation performance of circuit breaker of the air-insulated switchgear is improved. Finally
according to the electrical aging test
the four parameters including partial discharge
insulation resistance change
relative dielectric constant
and current leakage of the switchgear samples are taken as the indicators to analyze and characterize the electrical aging performances. The results show that
the four parameters can effectively reflect the real-time operation of air-insulated switchgear
so corresponding adjustment measures can be made in time to alleviate or avoid the aggravation of insulation deterioration and the occurrence of faults. The research work provides some data support and preventive measures for improving the insulation performance of air-insulated switchgear.