Study on Parameter Coordination Characteristics of Arrester with Parallel Gap for 110 kV Transformer Neutral Point
In order to reduce the short-circuit current when single-phase grounding happened
a large number of transformer neutral points in 110 kV system are not grounded. These transformer neutral points is facing serious overvoltage threat and many damage accidents occur. Aiming at the problems of complex structure
blind area and limitation of traditional protection methods
a new type of protection method with parallel gap arrester is proposed. Structural and performance characteristics of arrester with parallel gap is analyzed. The workload of main unit and parallel unit as well as the influence of resistor parameters and gap parameters in parallel unit on voltage distribution characteristics under continuous power frequency voltage and impulse voltage are studied through the test. The results show that under the power frequency voltage
the parallel gap can reduce the voltage of parallel unit
and the more the number of resistance pieces of the parallel unit
the greater the impact of the gap on the voltage ratio;under the impulse voltage
the impact of the parallel gap on the voltage of the parallel unit can be ignored. Finally
the configuration parameters of arrester with parallel gap for 110 kV transformer neutral point are given.