YAN Tao. Detection Method of SF6 Leakage in Gas Insulated Power Equipment Based on Wavelet Analysis[J]. High voltageapparatus, 2020, 56(10): 233-238. DOI: 10.13296/j.1001-1609.hva.2020.10.036.
Detection Method of SF6 Leakage in Gas Insulated Power Equipment Based on Wavelet Analysis
gas leakage detection method for insulated power equipment has the disadvantages of low detection accuracy and inability to accurately locate the leak point. Therefore
a method for detecting SF
6
gas leakage in insulated power equipment based on wavelet analysis is proposed. The infrared gas leak detector is used for sampling
the image preprocessing is realized by histogram equalization
the signal and the image are decomposed by wavelet transform
the background is
removed by wavelet transform
the target and noise are left
and the noise is removed by setting a wavelet threshold
so far
the design and implementation of SF
6
gas leakage detection method for insulated power equipment based on wavelet analysis has been completed. From the two aspects of detection accuracy and leakage point location accuracy
the SF
6
gas leakage detection method and the traditional detection method in the proposed insulated power equipment based on wavelet analysis are Comparative experiment. The experimental results show that compared with the traditional SF
6
gas leakage detection method in insulated power equipment
the SF
6
gas leakage detection method based on wavelet analysis is proposed. The detection accuracy is improved by dozens of times and the detection accuracy can reach 0.000 1 mL/s
and the positioning accuracy of the leak point is higher