PENG Jing, DENG Yunkun, ZHAO Xianping, et al. Research and Design of 40.5 kV Double-break Vacuum Circuit Breaker for Reactive Power Switching[J]. High voltageapparatus, 2020, 56(11): 39-45.
PENG Jing, DENG Yunkun, ZHAO Xianping, et al. Research and Design of 40.5 kV Double-break Vacuum Circuit Breaker for Reactive Power Switching[J]. High voltageapparatus, 2020, 56(11): 39-45. DOI: 10.13296/j.1001-1609.hva.2020.11.007.
Research and Design of 40.5 kV Double-break Vacuum Circuit Breaker for Reactive Power Switching
Aiming at the overvoltage problem caused by the high probability of restriking when 40.5 kV vacuum circuit breaker switching the capacitor bank and multiple reburning when switching the reactor
it is one of the feasible solutions to use double-break technology for reactive power switching.Therefore
in this paper
the key technology of a 40.5 kV double-break vacuum circuit breaker was researched.The experimental method for measuring insulating properties was given and the influence law of grading capacitance on power frequency and lightning impulse insulation characteristics was obtained.Then
the influence of contact material on the reactive power switching performance of vacuum interrupter was studied
optimized design of special vacuum interrupter and solid-insulation-embedded pole was proposed.On this basis
a 40.5 kV double-break vacuum circuit breaker was developed and the related performance verification test was carried out to meet the requirements of power system.