Experiment Research on Breaking Capability of Mechanical Type HVDC Circuit Breaker
High voltage DC circuit breaker(HVDC) is the foundation and security guarantee of the interconnection of HVDC and HVDC systems.It can not only break short circuit current but also break small load current
so as to realize the protection and control of HVDC system.In this paper
the performance of mechanical high voltage direct current circuit breaker breaking large current and small current in oscillation circuit is tested.The recovery voltage and the recovery voltage change rate of the mechanical HVDC circuit breaker were respectively tested when the 17.5 kA and 50 A currents were cut off.In the experiment
it is found that the mechanical HVDC circuit breaker can break off at the first zero point when the high frequency oscillating current is superimposed when the 17.5 kA current is broken
but it needs to be broken at the second current zero point when the 50 A current is broken.When the 50 A current is switched off
the recovery voltage and the recovery voltage change rate of the mechanical circuit breaker are larger than the corresponding value when breaking the 17.5 kA current.The test results will help us to understand the performance of HVDC circuit breakers in a comprehensive way.