Single-phase Grounding Fault Analysis of a GIS in a 220 kV Substation and Treatment Measures
Aiming at a single-phase grounding fault of a GIS in a 220 kV substation
the failure disconnector is disassembled and inspected both at the site and returned to the factory.The moving and static contacts
basin-type insulator
inner wall of the shell and the grading shield are inspected.The electric field simulation is carried out on the disconnector by finite element method.Comprehensive analysis shows that skewing of the grading shield and corrosion of the mechanical components cause deviation during the closing process of the moving and static contacts
results as poor contact of these two contacts.It generates partial discharge and causes breakdown between the middle contact and the shell.This is the reason of this fault.Comprehensive measures have been taken to deal with this fault
and the micro-water tests and UHF partial discharge detection tests are conducted to verify the treatment efficiency.Some reasonable suggestions are proposed for installation and daily maintenance of the GIS.