Experimental Research on the Depression of DC Offset of 500 kV Over Compensated Transmission Lines by Self-adaptive Successively Closing with Dynamic Phase Delays
|更新时间:2025-04-26
|
Experimental Research on the Depression of DC Offset of 500 kV Over Compensated Transmission Lines by Self-adaptive Successively Closing with Dynamic Phase Delays
High VoltageApparatusVol. 56, Issue 12, Pages: 277-285(2020)
ZHANG Jiaxin, WEI Yingli, ZHENG Xiongwei, et al. Experimental Research on the Depression of DC Offset of 500 kV Over Compensated Transmission Lines by Self-adaptive Successively Closing with Dynamic Phase Delays[J]. High voltageapparatus, 2020, 56(12): 277-285.
ZHANG Jiaxin, WEI Yingli, ZHENG Xiongwei, et al. Experimental Research on the Depression of DC Offset of 500 kV Over Compensated Transmission Lines by Self-adaptive Successively Closing with Dynamic Phase Delays[J]. High voltageapparatus, 2020, 56(12): 277-285. DOI: 10.13296/j.1001-1609.hva.2020.12.038.
Experimental Research on the Depression of DC Offset of 500 kV Over Compensated Transmission Lines by Self-adaptive Successively Closing with Dynamic Phase Delays
There is a large DC offset in the charging current after closing operation at one side of the no-load overcompensated line
which makes the charging current have no zero-crossing point for a long time.During this period
unexpected opening of the circuit breaker may cause the arc can not be extinguished even the breaker reaches its mechanical breaking point.Based on the analysis of the mechanism of DC offset
this paper proposes a phase angle control and self-adaptive delay sequential closing method for the first time
which combines the phase control closing technology and the charging current zero-crossing point detection technology
and solves the problem of arc-breaking in AC circuit breakers when the current is not zero-crossing effectively.Based on this method
the self-adaptive phase control and dynamic time-delayed sequential devices is developed and tested on three 500 kV over-compensation lines of Hebei south power.The dispersion of closing of 500 kV circuit breaker
the control precision of phase selection closing mode and the restraining effect on DC offset component are summarized in this paper.The engineering test shows that this method can effectively reduce the risk of DC offset after the no-load over-compensated line is closed.