Numerical Simulation Study on SF6 Leakage Characteristics in Shaft of UHV GIL Pipe
故采用数值模拟的方法进行研究。文中针对气体绝缘输电线路(gas insulated transmission line
GIL)管廊中的事故泄漏工况
考虑自然对流
进行三维建模
利用有限元计算进行了管廊竖井内SF
6
时间及空间分布特性的数值计算研究。结合苏通GIL综合管廊工程特点
研究了泄漏气体在管廊竖井内的空间分布特性
不同风速对泄漏气体排出时间的影响
以及在一定泄漏时长内竖井空间截面处气体体积分数的变化规律。结果表明:泄漏持续时
泄漏口附近体积分数最高
管廊左右两侧的竖井的SF
6
体积分数明显高于其他区域;泄漏气体在重力及主流作用下
团状高体积分数泄漏气体向竖井后下方转移;不同风量条件下
SF
6
体积分数分布基本相同;泄漏前期竖井最高体积分数迅速下降
泄漏后期体积分数缓慢下降;风机台数越少
SF
6
体积分数降至阈值以下需要时间更长。
Abstract
SF
6
gas
as a hidden danger of pipe leakage
has attracted more and more concern in engineering.The numerical simulation method is adopted for the study due to long transmission distance and complicated structure of the pipe and weak feasibility of the test and measurement method.For the accident leakage condition in the gas insulated transmission line(GIL) pipe
the 3-D model is set up by considering natural convection and the numeral calculation study of time and spatial distributio
n feature of SF
6
in the pipe shaft by the use of definite element calculation.The spatial distribution feature of the leakage gas in the pipe shaft is studied with combination of the project feature of Sutong GIL integrated pipe.The influence of different wind speeds on the discharge time of the leaking gas and the variation rule of the gas concentration at the spatial section of the shaft in a certain leak time are also studied.It is shown by the result that in case of continuous leakage
the concentration near the leakage port is the highest
and the SF
6
concentration of the shaft on the left and right sides of the pipe is significantly higher than that of other areas.Under the action of gravity and mainstream
the leakage gas with high concentration is transferred to the lower rear of the shaft.Under different air volume conditions
the concentration distribution of SF
6
is basically identical.The highest concentration of the shaft decreases rapidly in the early stage and gradually in the later stage.The small the number of fans is
Analysis of Coupled Structural Responses of Circuit and Equipment in Converter Substation Under Seismic Action
Simulation and Characteristic Analysis of Seismic Response of Coupling System of Flexible Conductors and Electrical Equipment in Substation
Numerical Simulation of Condensation and Influencing Factors Analysis of 10 kV High Voltage Switchgear
Research on Characteristics of Dielectric Barrier Discharge Load Under Pulse Excitation
Research and Mechanism Analysis of Electrically Induced Combustion Test Caused by Insulation Faults of Cable for Full-size High-voltage Switchgear Cabinet
Related Author
LI Guanghui
WANG Jinxiong
JIANG Weipeng
ZHANG Shihong
YANG Xu
LI Guanghui
LI Qiang
YU Jinyun
Related Institution
CSG Extra High Voltage Power Transmission Company, Dali Bureau
China Southern Power Grid Co., Ltd.
Electric Power Research Institute of EHV Power Transmission Company
Hubei Provincial Engineering Technology Research Center for Power Transmission Line, China Three Gorges University
College of Electrical Engineering & New Energy, China Three Gorges University