ZHANG Lei, YU Pengjun, LU Tianlin, et al. Operating Voltage Characteristics Analysis of Medium Voltage Side Reactive Power Compensation for UHV Transformer[J]. High voltageapparatus, 2021, 57(1): 100-107+115.
ZHANG Lei, YU Pengjun, LU Tianlin, et al. Operating Voltage Characteristics Analysis of Medium Voltage Side Reactive Power Compensation for UHV Transformer[J]. High voltageapparatus, 2021, 57(1): 100-107+115. DOI: 10.13296/j.1001-1609.hva.2021.01.015.
Operating Voltage Characteristics Analysis of Medium Voltage Side Reactive Power Compensation for UHV Transformer
UHV transformer reactive power compensation has such two types as medium-voltage side compensation and low-voltage side compensation.The low-voltage side reactive power compensation solution commonly used in China does not conform to the medium-voltage side reactive power compensation solution adopted by relevant international standards with some difference in both compensation effect and equipment cost.In view of 1 000 kV UHV autotransformer developed in China
the reactive power loss and influence of mid/low-voltage side compensation on the operating voltage is analyzed theoretically.Then PSCAD/EMTDC software is used to simulate analyze the fluctuation level and compensation effect of each bus voltage when reactive power compensation is performed on different sides of the UHV transformer.It is shown by the result that the voltage fluctuation due to reactive power compensation at medium voltage side of UHV transformer is lower than that in the low voltage side
which is beneficial for operation safety
high in compensation capacity and better in compensation efficiency.