Partial discharge live detector is widely used in the condition detection of power equipment
while
the Ultra-high frequency(UHF) sensor
as a kind of on-line monitoring device
is used widely in gas insulated switchgear(GIS) but is lack of site calibration method for the UHF sensor of GIS.For solving the difficulty of site calibration of UHF sensor of GIS
the on-site calibration method based on the picosecond level traveling wave is proposed in this paper.Firstly
the influence of different GIS structure such as the straight cylinders
corners
and insulating spacers on the attenuation and distortion is studied.Secondly
the effects of different traveling wave pulse injection methods on pulse waveforms and amplitudes are comparatively studied and the travelling wave injection mode for GIS at site is proposed.Finally
the on-site synchronous calibration study of distributed UHF sensors for GIS is carried out.The calibration method realizes the on-site synchronous calibration study of multiple UHF sensors in different positions in GIS is performed
which helps to accurately obtain the frequency response
bandwidth
sensitivity
etc.of the UHF detection system
and has positive advantages in improving partial discharge monitoring level and operating stability of the power system.