JIANG Ziyuan, TIAN Enwen, HE Bing, et al. Analysis on Exemption Conditions of OP1 in Out-of-phase Making and Breaking Tests of Circuit Breakers[J]. High voltageapparatus, 2021, 57(2): 21-26.
JIANG Ziyuan, TIAN Enwen, HE Bing, et al. Analysis on Exemption Conditions of OP1 in Out-of-phase Making and Breaking Tests of Circuit Breakers[J]. High voltageapparatus, 2021, 57(2): 21-26. DOI: 10.13296/j.1001-1609.hva.2021.02.004.
Analysis on Exemption Conditions of OP1 in Out-of-phase Making and Breaking Tests of Circuit Breakers
circuit breakers have complete type test requirements
one of which is out-of-phase making and breaking tests. GB/T 1984—2014 and DL/T 402—2016 have detailed de-scriptions of the out-of-phase making and breaking tests of circuit breakers
and both describe the exemption condi-tions for OP1
which means"If the 5% Isccritical current test is not required
OP1 can be omitted."This criteria hasbeen used for 20 years
with the progress of circuit breakers breaking principle
arc extinguishing method and manu-facturing technology
this criteria has been unsuitable in actual use.This article analyzes the system operating condi-tions
out-of-phase making and breaking tests and related tests principles
current domestic standards
find out thereasons for the defects in the current exemption conditions and proposes another exemption condition for OP1.