ZHOU Xiu, LIU Weifeng, TIAN Tian, et al. Health Condition Assessment Model of Power Transformer Considering Historical Condition[J]. High voltageapparatus, 2021, 57(2): 70-76.
ZHOU Xiu, LIU Weifeng, TIAN Tian, et al. Health Condition Assessment Model of Power Transformer Considering Historical Condition[J]. High voltageapparatus, 2021, 57(2): 70-76. DOI: 10.13296/j.1001-1609.hva.2021.02.011.
Health Condition Assessment Model of Power Transformer Considering Historical Condition
The structure and operation conditions of power transformer are complex and there are many factors thataffect its health condition.It is necessary to establish an effective evaluation model of transformer health condition toaccurately evaluate its condition.In this paper
a kind of health condition assessment model of transformer consider-ing the influence of historical operating conditions of transformer is proposed. Related important indicators are ex-tracted from such aspects as the oil chromatographic test
electrical test
oil chemical test data and field evaluation asquantitative and qualitative indicators.The preliminary evaluation results of transformer condition based on quantita-tive indicators are completed through subjective and objective combination weight and ridge membership function.The qualitative indicators are established with consideration of historical condition of the transformer to make reason-able correction of the preliminary evaluation result
so to complete the healthy condition evaluation of the transform-er. Finally
the effectiveness and accuracy of the evaluation method is verified by one set of 110 k V main transformerin Ningxia region.The health condition evaluation model of transformer proposed in this paper can provide referencefor intelligent operation and health management of transformer.