MA Yong, LIU Yongfei, GAO Shan, et al. Detection of C4F7N/CO2 Based on Fourier Transform Infrared Spectroscopy Technology[J]. High voltageapparatus, 2021, 57(3): 198-204.
MA Yong, LIU Yongfei, GAO Shan, et al. Detection of C4F7N/CO2 Based on Fourier Transform Infrared Spectroscopy Technology[J]. High voltageapparatus, 2021, 57(3): 198-204. DOI: 10.13296/j.1001-1609.hva.2021.03.030.
Detection of C4F7N/CO2 Based on Fourier Transform Infrared Spectroscopy Technology
which is widely used as insulating medium at present
is incontraction with the requirement of power system to the environmentally friendly
.Recently
C
4
F
7
N-CO
2
gas mix-ture
the environmentally friendly insulating medium
is considered to have a good engineering application pros-pect.Since the insulation performance of the gas mixture is closely related to the content of C
4
F
7
N and the gas pres-sure
the content of C
4
F
7
N gas mixture needs to be detected in the gas filling
exchange and maintenance in the ap-plication of future projects so to determine the actual concentration of the gas mixture.At present the related reportson the quantitative detection technology of C
4
F
7
N concentration in gas mixture is very rare.In this paper
the molec-ular configuration and spectrum optimization of C
4
F
7
N are performed based on the density functional theory and itsinfrared simulation diagram is obtained.Based on Fourier infrared spectroscopy(FITR)
the C
4
F
7
N/CO
2
gas mix-ture infrared detection platform is set up
the infrared absorption characteristic of C
4
F
7
N is analyzed with combina-tion of experiment and simulation.Moreover
the C
4
F
7
N characteristic infrared absorption band for concentration de-tection is determined in accordance with detection requirement at site
the quantitative detection of C
4
F
7
N in theconcentration range of 2%~10%is realized and the relative error of concentration detection does not exceed 5%.Thepeak is processed in accordance with Gaussian algorithm and the relative error of the concentration detection is re-duced to not more than 3%.The related research results provide important technical and theory reference for the rap-id detection of C