Study on Suppressing VFTO of 1 000 kV GIS Disconnector by Closing Resistor
In order to obtain more reasonable value of the closing resistor in the VFTO suppression of the GIS disconnector
a dynamic arc model consisting of hyperbolic resistance model
2~5Ω constant resistance model and Mayr arc model is adopted to describe the stage of pre-arcing
steady arcing and arc interruption of arcing model.The optimal VFTO suppression value at each stage of arc is obtained by way of changing the resistance of the closing resistor at various stages of dynamic arc model
and the average of the optimal resistance of various stages are taken as the optimal resistance of the closing resistor.Combined with certain 1 000 kV UHV substation
the extreme value of VFTO in its internal key equipment is analyzed.The obtained average value of optimal resistance of VFTO for GIS disconnector by way of simulation and analysis is 700Ω.Finally
the obtained optimal resistance is substituted into the dynamic arc circuit model for analysis and it is concluded that the suppression result of the shunt closing resistor to VFTO is remarkable.The optimal closing resistance at various stages of the arc is extracted to confirm that the optimal resistance for suppressing VFTO has more accuracy and reasonableness.