Fault Mode Analysis on Vacuum Contactor Based on Simulation and Test
it is difficult to install the displacement sensor due to small volume of the vacuum contactor and integration of drive
support and insulation part. Therefore
the operation characteristic of the contactor can be judged by the easily obtained current waveform of the opening and closing coil. A dynamic simulation model of the electromagnetic mechanism of the vacuum contactor is set up for the purpose of achieving the transverse comparison of current waveforms of the opening and closing coil at different conditions. It is found by comparing with the actually measured coil current and armature displacement curve that the error is within 10%.Then
the effects of mechanical jam
inter-turn short circuit of coil
voltage abnormity of coil and excessive core clearance on the current of coil are simulated and analyzed by quantitative method
finding that the model error meets the requirement of products and projects.