LI Qiang, CHEN Di, LI Bo, et al. Analysis on Small Capacitive Current Switching Test of Air-insulated Disconnector[J]. High voltageapparatus, 2021, 57(6): 216-221.
DOI:
LI Qiang, CHEN Di, LI Bo, et al. Analysis on Small Capacitive Current Switching Test of Air-insulated Disconnector[J]. High voltageapparatus, 2021, 57(6): 216-221. DOI: 10.13296/j.1001-1609.hva.2021.06.028.
Analysis on Small Capacitive Current Switching Test of Air-insulated Disconnector
The test circuit on small capacitive current switching test of air-insulated disconnector specified by the standards and its theoretical analysis in the standard are introduced.Combining with the wave form gained in the actual test
the difference of the wave form between this test circuit and the standard circuit of air-insulated disconnector test without inductance and with only low capacitance value at the source side is compared and analyzed.The characteristics
such in the standard circuit the peak over voltage to earth at both sides of the disconnector is more even
the arcing time is longer and the transient current during restriking is higher
are obtained.And the circuit is recommended to be adopted for the small capacitive current switching test of air-insulated disconnectors.