Electric Field Analysis and Optimum Design of Electric Field in Isolation Part of 35 kV Bypass Switch
In view of insulation design optimization for 35 kV bypass live operation equipment(35 kV bypass switch)which is lack of mature product design and experience reference both at home and abroad
the 3D modeling and simulation of it are performed based on finite element software MAXWELL and electric field distribution at the disconnector-the part with most serious electric field concentration
is analyzed
finding small gas gap between the high voltage part and insulating part can lead to the phenomenon of local electric field concentration and discharge. At the same time
the adoption of appropriate break distance and electrode shape can also improve the electric field distribution.