LIU Yichen, YU Jingzhe, CHEN Xiangrong, et al. Insulation Condition Assessment of XLPE Cable in AC Distribution Network Under Water Environment Based on TOPSIS-RSR Method[J]. High voltageapparatus, 2021, 57(7): 105-111+118.
DOI:
LIU Yichen, YU Jingzhe, CHEN Xiangrong, et al. Insulation Condition Assessment of XLPE Cable in AC Distribution Network Under Water Environment Based on TOPSIS-RSR Method[J]. High voltageapparatus, 2021, 57(7): 105-111+118. DOI: 10.13296/j.1001-1609.hva.2021.07.015.
Insulation Condition Assessment of XLPE Cable in AC Distribution Network Under Water Environment Based on TOPSIS-RSR Method
A large number of AC distribution cable in southern China
especially in coastal areas
operate in water environment for a long time. Accurate assessment of the insulation performance of the cable under water environment is of great significance to the safe and stable operation of power grid. Eighty groups of 10 kV AC distribution network XLPE cables operating under different environmental conditions and loads are selected. The insulation condition of the selected cables are assessed by the comprehensive evaluation method of ideal solution-rank sum ratio and
at the same time
ultra-low frequency dielectric loss and oscillating wave partial discharge experiments are carried out on the selected cables and the effects of moisture and temperature on the insulation performance of the cables are studied in particular. The accuracy of the insulation condition assessment result of the cables is proved by the experimental results of ultra-low frequency dielectric loss and oscillating wave partial discharge. Therefore
before the insulation detection of multiple pieces of cables
the insulation condition of the cables to be tested can be evaluated by the comprehensive evaluation method of ideal solution-rank sum ratio so as to improve the maintenance efficiency of AC distribution network cables.