HE Xingrong, YIN Jia, ZHANG Guozhi, et al. Study on Pressure Uariation Characteristics of Oil-minimum Equipment Under Overheat Defects[J]. High voltageapparatus, 2021, 57(8): 99-104.
DOI:
HE Xingrong, YIN Jia, ZHANG Guozhi, et al. Study on Pressure Uariation Characteristics of Oil-minimum Equipment Under Overheat Defects[J]. High voltageapparatus, 2021, 57(8): 99-104. DOI: 10.13296/j.1001-1609.hva.2021.08.014.
Study on Pressure Uariation Characteristics of Oil-minimum Equipment Under Overheat Defects
In view of insufficient dielectric online detection technology of existing minimum oil electrical equipment
in recent years
some scholars have proposed pressure-based online monitoring technology of minimum oil equipment. However
internal pressure variation characteristic of minimum oil equipment at overheat defect has not been experimentally studied by scholars. In this paper
110 kV oil immersed vertical currnt transformer is taken as prototype to study by experiment the internal pressure variation characteristic of minimum oil equipment at the temperature of 100 ℃
150 ℃
200 ℃
250 ℃ and 300 ℃ respectively. It is shown by the result that(1)the pressure variation by mild and low temperature overheat defects is small and the maximum increments in 50 hours is 1.33 k Pa
1.65 kPa
2.01 kPa
2.51 kPa
and 2.70 kPa
respectively;(2)the pressure variation due to overheat defect shows exponential increase. In the initial 10 hours
the pressure rises sharply and gradually in 10~20 hours. The pressure remains basically unchanged after 20 hours.(3)The increase range the maximum pressure with 50 hours is several hundreds of Pascals at every 50 ℃ rise in the temperature of the overheat spot. At the same time
three reasons with different pressure variation characteristic due to overheating and discharge defects are pointed out by theoretical analysis.