Comparative Analysis on Simulation of AMF and TMF High Frequency Magnetic Field Characteristics
The arc interruption performance of vacuum interrupter is closely related to the magnetic field characteristics of the vacuum interrupter contacts.Both axial magnetic field(AMF)and transverse magnetic field(TMF)arc interruption technologies are the most commonly used technologies.HVDC vacuum circuit breaker based on artificial zero-point introduces high-frequency oscillating current to help interruption.In order to analyze the magnetic field characteristics of the vacuum circuit breaker under high-frequency current
two types of contact structures are set up for finite element simulation.The magnetic field characteristics of the vacuum interrupter and the eddy current of the contact piece are compared and analyzed.The result shows that
in case of high frequency current interruption
the contact of transverse magnetic structure has better magnetic field characteristic distribution than that of longitudinal magnetic structure.The eddy current of the contact piece is the key factor causing deterioration of magnetic characteristic of contact with axial magnetic structure and
however
has almost no influence on the magnetic field characteristics of the transverse magnetic contact gap.