CHAO Yafeng, WAN Tao, ZHANG Liu, et al. Analysis and Suggestions on String Breakage Failure of Composite Insulator of Overhead Transmission Line in Hunan Power Grid[J]. High voltageapparatus, 2021, 57(8): 209-215.
DOI:
CHAO Yafeng, WAN Tao, ZHANG Liu, et al. Analysis and Suggestions on String Breakage Failure of Composite Insulator of Overhead Transmission Line in Hunan Power Grid[J]. High voltageapparatus, 2021, 57(8): 209-215. DOI: 10.13296/j.1001-1609.hva.2021.08.028.
Analysis and Suggestions on String Breakage Failure of Composite Insulator of Overhead Transmission Line in Hunan Power Grid
In view of string breakage problem of composite insulator in Hunan Power Grid of last 10 years in
the string breakage case is statistically analyzed
finding that the string breakage probability of 500 k V line is higher.There are two types of breakages out of the 7 times
one type is 6 times of insulator proper damage and the other type is 1 time of unreasonable design.In the former type 2 times are core brittle fracture and 4 times are core bar brittle breakage.10 pieces of samples are selected for mechanical and electrical tests in the laboratory.The same batch of samples were not found to be unqualified by mechanical damage load
anti-leakage tracking
acid resistance test of core bar and autopsy test and so on.The optimization suggestion of sampling test items of the composite insulator is proposed.The key items of access detection of composite insulator of EHV transmission lines in severe string breakage area is recommended and
at the time
specific operational suggestion for the special patrol inspection of composite insulator is proposed.